TA05 İnteraktif Heat Detector
TA05 temperature heat detector analyzes the ambient temperature by the means of thermistor type CTN. TA05 is able to detect elevation of temperature corresponding to A1S, A2S, BS, A1R, A2R, and BR class according to EN54-5 standard. The various levels of temperature are chosen while programming: - Static temperature detector: • TA05-A1S: static T°=62°C+5/-3°C • TA05-A2S: static T°=68°C+5/-3°C • TA05-BS: static T°=75°C+5/-3°C - Static + rate of rise temperature detector: • TA05-A1R: static T°=62°C+5/-3°C • TA05-A2R: static T°=68°C+5/-3°C • TA05-BR: static T°=75°C+5/-3°C TA05 includes a developed technology (microprocessors, smd components) which means precision and high reliability. A specific head detection fixed by a single ceiling base. TA05 is dedicated to analogue fire detection panels. Temperature heat detectors are designed to be installed under flat ceiling with heights ranging between 2,5 m and 6 m (3,5m for A1S, A2S and BS class) in healthy and more or less ventilated buildings. The maximum supervised surface is 35m² by detector; however it is preferable to refer to the local rules of installation recommended in particular when the characteristics of the installation differ from those stated above